Products  Fans  By Application  Filter Supply Inline – FSD354ER
Print Friendly Version

Filter Supply Inline – FSD354ER

Filter Supply Inline

Performance Curve - FSD354ER

Description

The Inline Filtered Supply Unit has been designed to provide filtered outside air to a range of applications where direct fresh air intake is not possible or practical.
Features
  • Robust, yet lightweight galvanised steel construction
  • Mixed-flow impeller with high performance blade geometry
  • Pure-V washable G4 filters on the fan discharge side that can
  • be easily accessed via a removable side panel
  • Choice of external rotor motors available in single phase
  • and 3-phase configurations
  • Supplied with TDF flanges as standard for inline mounting or
  • installed with an external grille for flush to wall mounting
Construction
Galvanised steel housing with material filters on the discharge side of the fan.
Industry standard 35mm TDF profile flange for easy connection to ducting.
Motors

Type – external rotor squirrel cage induction motor

Electricity supply - 230V, single-phase and 415, 3 phase, 50Hz

Bearings – sealed-for-life, ball

3-phase motors can be speed controlled using variable speed drives

Internal Thermal Protection

Auto-reset type fitted as standard

Testing

Air flow tests based on ISO 5801.

Noise tests based on ISO 13347-3.

Performances shown are based on clean filters.

As air flow will be affected by room pressurisation, care should be taken to ensure adequate air relief is provided.

Special Note

Pure-V filters

The Inline Filtered Supply Unit incorporates Airepure Pure-V filters that are pleated for extra durability and will hold their shape without the need of a wire support metal cage. Pure-V panel filters are washable.

The filters should be checked during cleaning for wear or damage and replaced when necessary. They can be removed via the side access panel on the discharge side of the fan.

Airepure Pure-V filters are tested with an efficiency of G4 to standard EN 779:2002.

Differential Pressure Switch

A differential pressure switch can be used to provide indication that the filter needs maintenance.

Special Features

The Inline series of Filtered Supply Units shall be designed and manufactured by Fantech Pty Ltd and be of the model numbers shown on the schedule/ drawings.

The unit will have a galvanised steel housing with 35mm TDF profile flange connections and incorporate a weatherproof external grille if mounted flush to an external building wall. It will include Pure-V washable G4 filters on the discharge side of the fan.

The unit shall incorporate a Mixed-Flow impeller made from high performance injected moulded composite plastic and driven by an external rotor motor as nominated.

All performance data shall be for a complete assembled unit, and based on ISO 5801 for air flow and ISO 13347-3 for noise.

Technical Data - FSD354ER

Speed [rps]Avg. dBA @ 3mkWatts (Input)Amps Max.°C Approx. Weight [kg]
230.330.686043

Sound Data

Type631252505001K 2K4K8K
Inlet6568 615854 565549
Outlet6667 616062 605852

Dimensions

ABCD
820783750630

*All dimensions in mm, unless otherwise stated