Products  Fans  Energy Efficiency  Gamma Downflow Series – CD316D
Autocad  Print Friendly Version

Gamma Downflow Series – CD316D

Gamma Downflow Series

Performance Curve - CD316D

Description

The Gamma Series of centrifugal roof units has been designed for use in commercial ducted exhaust applications. These compact and low profile units are fitted with birdmesh to prevent the entry of birds and vermin into the ducting or building. They are available in 12 sizes, extending from 192 to 710mm diameter.
Features
  • Robust, lightweight construction.
  • Choice of speeds available.
  • Compact, low profile design.
  • Designed for down flow exhaust applications.
  • Twin vertical discharge fan also available. Provides 100% standby capacity.
  • Shutters are standard on twin fan units and an optional extra for single fan units. The pressure loss across the shutter has to be added to the system pressure before making selections.
  • Can be mounted at angle up to 30°.
  • Most 3-phase motors are 2-speed star/delta design.
  • Supply air units can be supplied
  • Construction
    Cowls are UV-stabilised plastic.
    Impellers are backward-curved centrifugal design and can be plastic, steel or aluminium.
    Steel components have a corrosion resistant finish.
    Bird-mesh guards are fitted as standard to both downflow and vertical exhaust models.
    Motors
    Type - external rotor, squirrel cage induction motor
    Electricity supply - 230V, single and 415V, three-phase, 50Hz
    Bearings - sealed-for-life, ball
    Speed-controllable using electronic or auto-transformer controllers (except CE316)
    Most three-phase units are fitted with 2-speed star/delta design motors
    Internal Thermal Protection
    Thermal protection is supplied as standard on all motors.
    Testing
    Air flow tests to ISO5801:2007
    Noise tests to BS848:Part 2, 1985

    Suggested Specification

    The Gamma Series of centrifugal roof ventilators shall be the downflow exhaust type as designed and manufactured by Fantech Pty. Ltd.
    Impellers shall be backward-curved centrifugal design and driven by speed-controllable external rotor motors with integral thermal protection.
    The cowl shall be of the downflow exhaust design and formed from plastic and/or fibreglass. Steel components are corrosion protected.
    All models shall be fully tested as a complete assembled unit to ISO5801:2007 for air flow and BS848:Part 2, 1985 for noise.

    Technical Data - CD316D

    Speed [rps]Avg. dBA @ 3mkWatts (Input)Amps Max.°C Approx. Weight [kg]
    18420.10.16608

    Sound Data

    Type631252505001K 2K4K8K
    Inlet7668 646054 544842

    Dimensions

    ABCDEFG
    31041075500575350334

    *All dimensions in mm, unless otherwise stated

    Wiring Diagram


    Diagram shown is for single-speed only.
    For 2-speed and special motors, contact Fantech for details.

    Ancillaries

       
    Elta Group