Flameproof Miniduct – FPMD354
Performance Curve - FPMD354
Description
The Compact Series of Flameproof Miniduct fans has been specifically designed for duct mounting and to ventilate hazardous or explosive environments.
There are 4 sizes in the range extending from 250 to 400mm
diameter.
Features Galvanised steel casing with red powder-coated finish.
Anti-static blades.
Suitable for ducted installations.
Can be mounted at any angle.
Designed for single-phase supply.
Motors comply with Ex d, Group II, Zone 1, T6 protection - see Special Note. IP66 rated.
Construction
Galvanised steel casing with red powder-coated finish.
Axial impellers have glass reinforced anti-static blades.
Motors
Type - squirrel cage induction motor.
Electricity Supply - 230V, single-phase, 50Hz.
Bearings - sealed-for-life, ball
Maximum ambient temperature 40 °C.
These motors are not speed-controllable.
Internal Thermal Protection
The motor is fitted with thermal protection to conform
to the requirements of AS1359. IECEx certification and
classification of T6 does not take into account abnormal
operation such as locked rotor where the temperature
of the surfaces may exceed 85°C. If this is an issue with
your application, further protection should be fitted.
Testing
Air flow tests to ISO5801:1997, 'Type 'D' Installation
(ducted inlet and outlet).
Noise tests to BS848:Part 2, 1985.
Special Note
These products have a Certificate of Conformity issued under the IEC Ex Certification Scheme for Explosion Protected Electrical Equipment.
This certificate, number IEC Ex TSA 14.0024X, covers these fans for Ex d GroupII, Zone 1 protection. These fans are approved for gas Groups llA, llB and llC, have temperature classification T6 and enclosure protection IP66.
Suggested Specification
The fans shall be of the Compact Flameproof Miniduct Series, as designed and manufactured by Fantech Pty Ltd and shall be of the model numbers shown on the schedule/drawings.
They shall be approved for gas Groups llA, llB and llC, have temperature classification T6 and enclosure protection IP66.
They shall have a galvanised steel casing with a red powder-coated finish and be fitted with glass reinforced anti-static blades.
All data shall be based on tests to ISO5801:1997, Type 'D' Installation for air flow and to BS848:Part 2, 1985 for noise.Technical Data - FPMD354
Speed [rps] | Avg. dBA @ 3m | kWatts (Input) | Amps | Max.°C | Approx. Weight [kg] |
---|
23 | 50 | 0.12 | 1 | 40 | 16 |
Sound Data
Type | 63 | 125 | 250 | 500 | 1K | 2K | 4K | 8K |
---|
Inlet | 67 | 80 | 71 | 66 | 62 | 61 | 57 | 51 |
Dimensions
*All dimensions in mm, unless otherwise stated
Ancillaries