Autocad  Print Friendly Version

Ezifit Thru Roof Exhaust Fan - Bushfire Code Compliant (BAL-40) – ECE154-BFC

Ezifit Thru Roof Exhaust Fan - Bushfire Code Compliant (BAL-40)

Performance Curve - ECE154-BFC

Description

The Ezifit Roof Series, with BAL-40 bushfire code compliance, has been developed and tested for exhaust air applications in bushfire prone regions. They are driven by a high performance centrifugal fan and have a low profile design. They can exhaust from a number of points within the building and are available in 150 and 200mm fan sizes.
Features
  • Robust, galvanised steel construction.
  • Speed-controllable with electronic controller.
  • High performance, low noise backward-curved centrifugal impellers.
  • High quality bronze mesh provides ember protection.
  • Comes with convenient 3-pin plug and lead.
  • Designed for downflow discharge.
  • Can be mounted at angles up to 30°.
  • Powder coated finish is an optional extra.
  • Compliant to AS3959:2009 up to and including BAL-40.
  • Construction
    Cowls are of galvanised steel
    Ember protection - bronze mesh with max. 2mm aperture
    Backward-curved centrifugal impellers
    3-pin plug and lead included
    Motors
    Type - external rotor, squirrel cage induction motors
    Electricity supply - 230V, single-phase, 50/60Hz
    Bearings - sealed-for-life, ball
    Can be speed controlled
    Internal Thermal Protection
    ECE152-BFC & ECE154-BFC - Manual-reset type
    ECE204-BFC - Auto-reset type
    Testing
    Air flow to ISO5801:2007
    Based on noise tests to BS848:Part 2, 1985
    Special Note
    Construction of buildings in bushfire prone areas
    AS3959:2009, clause 6.6.5(b) "Roof penetrations" states: Openings in vented roof lights, roof ventilators or vent pipes shall be fitted with ember guards made from a mesh or perforated sheet with a maximum aperture of 2mm, made of corrosion-resistant steel, bronze or aluminium.

    Suggested Specification

    The roof ventilators shall be of the Ezifit Roof Series with bushfire code compliance as designed and manufactured by Fantech Pty Ltd.
    The backward-curved centrifugal fans shall be direct-driven by continuous rated, speed-controllable external rotor motors with thermal protection.
    They shall be constructed from galvanised steel, be of downflow discharge design and include a 3-pin plug and lead.
    Ember protection mesh shall be bronze or steel with openings a maximum of 2mm.
    All data shall be based on tests on a complete assembled unit according to ISO5801:2007 for air flow and BS848:Part 2, 1985 for noise.

    Technical Data - ECE154-BFC

    Speed [rps]Avg. dBA @ 3mkWatts (Input)Amps Max.°C Approx. Weight [kg]
    23350.030.16604

    Sound Data

    Type631252505001K 2K4K8K
    Inlet5352 575548 433627

    Dimensions

    ABCDE
    20025055256286

    *All dimensions in mm, unless otherwise stated